34 — ElectriCalc LT

Finding Voltage Drop Wire Size

A 20-amp single-phase 208-volt load
will be located 175 feet away from the
source. Assuming a 3% allowable volt-
age drop, what is the size of 75°C con-
ductor required for this branch circuit?

Steps Keystrokes Display

Reset calculator

[Set] [x]

0.

Set to 75°C

[Set] 7

3Ø 75 Cu 0.

Set to single ph.

[Set] 1

1 PH

Enter amps

20 [Amps]

20. AMPS

Enter volts

208 [Volts]

208. VOLT

Enter distance

175 [Length]

175. FEET

Enter allow. VD% 3 [VD%]

3 DROP V %

Find wire size

[WireSz]

8 CU

AWG WIRE SIZE

Find actual
voltage drop

[VD%]

5.4 DROP V

Find % v.drop

[VD%]

2.6 DROP V %