Motor horsepower, Finding single-phase full load current – Calculated Industries 5065 User Manual

Page 36

Advertising
background image

User’s Guide — 31

The

ElectriCalc Pro can calculate the

full load current (Amps) of a motor,
based on phase, Voltage and motor
(synchronous, induction, or DC). It uses
NEC Tables 430-247, 430-248 and
430-250 to determine the motor full load
current. (If you enter a value for HP or
Voltage that does not correspond to
these tables, the unit will display nonE).

The

ElectriCalc Pro can also calculate

an equivalent Horsepower for an induc-
tion, synchronous or direct current motor
based on a Voltage, phase and full load
current. When calculating motor HP from
an entered amperage, a result not
directly matching a value in NEC Table
430-247, 430-248 or 430-250 will cause
the calculator to choose the next higher
table value for motor Horsepower.

Finding Single-Phase Full Load
Current

A 2 HP induction motor operates on 230
Volt, single-phase power. What is the full
load current for this motor?

Steps

Keystrokes

Display

Clear calculator

o o

0.

Set to 1-phase

S 1

1 PH

Enter Volts

2 3 0 U VOLT 230.

Enter HP

2 h

IND 2. HP

Find full load Amps

A

FLC 12. A

Motor Horsepower