Re-sizing Wire Based on
Different Insulation Ratings

What wire size is required for a 3Ø, 75°C
copper branch circuit carrying a load of
260 Amps? What would the wire size be
if 90°C copper is used?

Steps

Keystrokes

Display

Clear calculator

o o

0.

Set to 3-phase

S 3

3 PH

Set to 75°C

S 7

3Ø 75 Cu 3 PH

Enter Amps

260 A AMPS 260.

Find wire size

w

AWG 300 CU

WIRE SIZE

Change to 90˚

S 9

AWG 0000 CU

WIRE SIZE

Reset to 60˚

S 6 o 3Ø 60 Cu 0.

and Clear

Wire Sizing Based
on Ambient Temperature

Find the 90°C copper wire size needed
to connect a 47,700 Volt-amp load to a
240 Volt, single-phase source. What is
the adjusted wire size, if the ambient
temperature rating is changed from the
default 30°C to 40°C?

Steps

Keystrokes

Display

Clear calculator

o o

0.

Set to 1-phase

S 1

1 PH

Set to 90°C

S 9

1Ø 90 Cu 1 PH

Enter VA

4 7 7 0 0 V

VA 47,700.

(Cont’d)