52 — ElectriCalc Pro

Finding Motor Branch-Circuit
Wire Size and Conduit Size —
Same Wire Type & Size

What size THHN copper wire and RMC
conduit are needed to connect a 10 HP
1Ø induction motor to a 115 Volt source?

Steps

Keystrokes

Display

Clear calculator

o o

0.

Set to 1-phase

S 1

1 PH

Set to 60º C

S 6

1Ø 60 Cu 1 PH

Enter Volts

1 1 5 U VOLT 115.

Enter Horsepower

1 0 h

IND 10. HP

Enter cond. type

8 S C RMC nonE

Display full load

Amps

A

FLC 100. A

Find wire size

S w

AWG 0 CU

WIRE SIZE 125%

Find wire ampacity

w

0 125.0*

WIRE A125%

Find conduit size

C

RMC 1.25 in

COND SIZE

Find total # wires

C

2. TTL WIRES

Find conduit fill %

C

FILL 24.3

COND %

Find act. fill area

C

FILL 0.3710

TTL WIRE AREA

Find rem. area

C

REM 0.1021

WIRE AREA

Set to 3-phase

S 3 o 3Ø 60 Cu 0.