Finding single-phase voltage drop – Calculated Industries 5065 User Manual

Page 47

Advertising
background image

42 — ElectriCalc Pro

IMPORTANT NOTE ON

VOLTAGE DROP CALCULATIONS

The

ElectriCalc Pro calculates Voltage

drop and wire size using DC resistance as
defined by the 2005 NEC. To find the
Voltage drop for a

specific wire size, you

must

first enter Amps and the one-way

wire Length (and other required variables),
entering the specific wire size

last.

Otherwise, for your safety the calculator
will recalculate the wire sizes based on
the ‘99 NEC Ampacity Tables and maxi-
mum allowable Voltage drop.

Finding Single-Phase Voltage Drop

You are installing 175 Feet of 75°C, #8 THW
branch circuit copper conductors to supply
an 11A load on a 208V 1Ø system. What is
the source Voltage drop at the load?

Steps

Keystrokes

Display

Clear calculator

o o

0.

Set to 1-phase

S 1

1 PH

Set to 75°C

S 7

1Ø 75 Cu 1 PH

Enter Amps

1 1 A

AMPS 11.

Enter Volts

2 0 8 U VOLT 208.

Enter Length

1 7 5 l FEET 175.

Enter wire size*

8 w

AWG 8 CU

WIRE SIZE

Solve volt. drop

v

DROP 3.0 V

Solve % v.drop

v

DROP 1.4 V %

* Wire size can also be entered in Circular
Mils (e.g.,

1 6 5 1 0 w

enters

16,510 CMILs and displays 8 AWG wire
size).