38 — ElectriCalc Pro

Sizing Parallel Conductors

What size 60°C insulated copper wire is
required for a single conductor carrying a
500 Amp load in a Free Air environment
(30°C amb. temp.)? What size for 2 par-
allel conductors? For 3 conductors?

Steps

Keystrokes

Display

Clear calculator

o o

0.

Set to 60°C

S 6

3Ø 60 Cu 0

Set free air mode

S 5 3Ø 60 FrAir Cu 0.

Enter Amps

5 0 0 A AMPS 500.

Find 1 wire size

w

AWG 500 CU

FrAir WIRE SIZE

Find 2 wire size

2 P

PAR 000 CU

FrAir WIRE SIZE

Find 3 wire size

3 P

PAR 0 CU

FrAir WIRE SIZE

Exit Free Air Mode

S 5 o 3Ø 60 Cu 0.

and Clear

NOTE: Parallel wire sizes smaller than
1/0 will be displayed as nonE.

NOTE: See “Settings” for a list of
Permanent Values/settings. Changing
these settings may affect your calculations.