Ampacity wire sizing, Wire sizing based on insulation rating – Calculated Industries 5065 User Manual

Page 39

Advertising
background image

34 — ElectriCalc Pro

The required wire size of a service con-
ductor can be determined based on the
specified electrical requirements and the

w

key. The wire size is automatically

recalculated whenever the wire insulation
(temperature) ratings or wire material (cop-
per or aluminum) types are revised. Wire
sizing is based on the requirements
defined in NEC Tables 310-16 and 310-17.

Wire Sizing Based on
Insulation Rating

Wiring is being installed in a 240 Volt,
single-phase system rated at 30 kVA.
What is the wire size needed if you use
60°C copper wire?

Steps

Keystrokes

Display

Clear calculator

o o

0.

Set to 1-phase

S 1

1 PH

Enter kVA

3 0 K V KVA 30.

Enter Volts

2 4 0 U VOLT 240.

Find Amps

A

AMPS 125.

Find wire size

w

AWG 0 CU

WIRE SIZE

Display Wire
Ampacity

w

0

125.0 Cu WIRE A

Display CMIL

w CMIL 105,600 WIRE

Display NEC Table

w

NEC 310.16

Ampacity Wire Sizing