Ground conductor wire size – Calculated Industries 5065 User Manual

Page 52

Advertising
background image

User’s Guide — 47

You can use single or multiple service
entrance conductor(s) to find the
grounding electrode conductor for AC
systems. When using multiple conduc-
tors, the

ElectriCalc Pro uses the

equivalent Circular Mils to find the
grounding electrode conductor (based
on NEC Table 250-66).

Find the grounding electrode conductor
wire size required when 2/0 is the larg-
est 3-phase 75°C copper service-
entrance conductor being used. What
is the equivalent aluminum size? What is
the equivalent Circular Mils?

Steps

Keystrokes

Display

Clear calculator

o o

0.

Set to 3-phase

S 3

3 PH

Set to 75º C

S 7

3Ø 75 Cu 3 PH

Enter wire size*

0 0 w AWG 00 CU

WIRE SIZE

Find ground wire

G

GRND 4 CU

size

WIRE SIZE

Find aluminum size

G

GRND 2 AL

WIRE SIZE

Find Circular Mils

G

CMIL 133,100.

WIRE

Display NEC Table

G

NEC 250.66

* Wire size can also be entered in Circular
Mils (e.g.,

1 3 3 1 0 0 w

enters

133,100 CMILs and displays 00 AWG wire
size).