2

HSI #780-0867

FireSpy Tracker Installation Manual

8

The main board contains (1) common alarm relay output, (1) common supervisory alarm relay output, and
(1) common trouble relay output, as well as a connection for up to (5) relay modules (T8000-RC).

Table 2-9: Output relay specifications (MB / MBC / MBCLC)

Parameter

Rating

Type

Form C (SPDT)

Contact rating
MBC / MBCLC

resistive load, PF=1.0


inductive load, PF=0.4


MB

resistive load, PF=1.0


10A @ 30VDC
10A @ 240VAC*
3A @ 240VAC*

2A @ 30VDC

*

Limited to 50VDC due to spacing

Table 2-10: SLC specifications (MB / MBCLC)

Parameter

Rating

Loop output voltage

32V @ 10kHz

Max loop output current

400mA max

Max loop capacitance

0.5uF

Max loop impedance (total per loop)

40 ohms

Environment

UL864 location

Temperature range

Maximum relative humidity


Indoor, dry
32 to 120° F
93%

*

See Appendix C Wire Selection for suggested wiring distances.

2.3.2 Display board (T-PDC)

The display board may mount either inside the enclosure door so its buttons are accessible with the door
closed or on the chassis assembly (MBC or MBCLC only) so it is accessible after unlocking and opening
the enclosure. When the PDC is mounted on the door and connected to the keyswitch, the keyswitch
must be activated to enable keypad access to the system’s security-sensitive control functions.

2.3.3 Network Communications adapter (T8000-NCA)

The network communications adapter is used with each panel in a networked system. It allows the
connected panel to communicate with other panels on the panel network.

Table 2-11: Communications adapter (T8000-NCA) specifications.

Parameter

Rating

Input voltage

Regulated 24 DC

Input current draw

60 mA

Max impedance, RS485 communication wiring, total

40 ohms*

Max capacitance, RS485 communication wiring

0.3 uF*

Environment

UL864 location

Temperature range

Maximum relative humidity


Indoor, dry
32 to 120° F
93%

*

See Appendix C Wire Selection for suggested wiring distances.