HSI #780-0867

FireSpy Tracker Installation Manual

4

2.2

System layout

2.2.1 Standalone panel

A Tracker panel consists of the main board (MB for T1000, MBC for T8000 or MBCLC for T2000) in the
main enclosure and various devices that connect to the main board (see Figure 2-2). System
programming can be done from a PC or laptop through the serial port of the panel’s communications
adapter.

2.2.2 Multiple panel network

A Tracker network consists of multiple Tracker panels with each panel connected to the network through
a communications adapter (see 2.3.3 Network Communications adapter (T8000-NCA)). Local network
devices (annunciators, etc.) connect to the RS485 outputs of each panel, as they would in a standalone
panel. Each panel provides the same capabilities as it would as a standalone panel, with the addition of
the network connection. System programming can be done from a PC or laptop through the serial port of
the panel’s communications adapter.

NOTE:

A Tracker network must include at least one T8000 panel, set up as master.

T1000 SYSTEM

(TO NETWORK)

TO PC

290-0158

* MAY BE INDIVIDUALLY CONFIGURED AS NAC, AUX POWER, OR INPUT
** MAY BE CONFIGURED AS NAC (FOR CONNECTION TO NAC BOOSTER OR VOICE MODULE) OR INPUT
A SYSTEM MUST USE AT LEAST ONE INITIATING DEVICE

MAIN BOARD ASS'Y
MB

RS485

(3) NACs*

(1) SLC

RELAY CONTACTS

(8) PER SRM

PHONE LINES

TO CENTRAL

OR REMOTE

STATION

RELAY

CONTACTS

(2) PER RC

RELAY CONTACTS
(2) PER RC

ANN
(7) MAX

IDC

(5) CLASS A OR

(10) CLASS B

PER CM

RC

(5) MAX

PER CM

CM
(6) MAX

SRM
(6) MAX

250 OUTPUTS

PER LDV

(250 TOTAL

CONFIGURABLE)

LDV
(4) MAX

RC

(5) MAX

USB

RELAY CONTACTS:
(1) SYSTEM ALARM
(1) SYSTEM SUPV ALARM
(1) SYSTEM TROUBLE

NCA

ANNUNCIATOR
(MOUNTED ON
MAIN CABINET
DOOR)

(1) AUX I/O**

1

2

3

4

5

6

7

8

9

10

SILENCE

POWER

ALARM

TROUBLE

SUPERVISORY

1

2

3

4

5

6

7

8

9

10

SILENCE

POWER

ALARM

TROUBLE

SUPERVISORY

Figure 2-2: System layout (T1000)