Table 2-19: City tie/reverse polarity communicator (UCT) specifications.

Parameter

Rating

Supply voltage

24V*

Input current draw

350mA max

Relay contacts
Trouble contacts
Alarm contacts


1A @ 28VDC, form C
5A @ 28VDC, form C

Remote station transmitter circuit outputs (power limited)**
Voltage
Current


16.5 – 24.6VDC
14mA max

Local energy city tie outputs (not power limited)
Standby voltage
Standby current
Alarm voltage
Alarm current
Ripple voltage (alarm)
Intended trip coil


18-40mVDC
1.5mA max
16-28VDC
270mA max (momentary load)
1.2V max
14.5 ohm

*

The same power source must be used for powering the UCT and relay contact wiring.

**

These circuits are to be supervised by the remote station.

2.3.13 Enclosures

Table 2-20: Enclosure dimensions and module mounting provisions.

T1-CAB

T8000-CAB
T2000-CAB

T2000E-CAB

T8000-EXP

Size (inches)
Overall
Backbox

W x H x D
15.88 x 25.19 x 4.8
14.5 x 23.5 x 4

W x H x D
15.88 x 25.19 x 4.8
14.5 x 23.5 x 4

W x H x D
19.25 x 33.25 x 4.5
18 x 32 x 4

W x H x D
11.37 x 15.44 x 3.8
10 x 14 x 3

Knockouts
(1-1/8 dia)

4 top
3 each side

4 top
3 each side

3 top, 2 bottom,
4 each side

3 top
3 bottom

Module

Quantity of modules that may be mounted

T1-MB

1

T8000-MBC or
T2000-MBCLC or

1

1

T8000-LCU

2*

2*

T8000-CM

2*

2*

T8000-SRM

1*

1*

T8000-RC

2

T-UDACT

1

T8000-NCA

1

25HAVE, 50HAVE,
or 100HAVE

1

ZSC-2A or ZSC-4B

2*

Batteries

(2) 12V, up to 12Ah**

(2) 12V, up to 12Ah**

(4) 12V, up to 18Ah†

*

A total of two mounting locations are provided for a combination of these modules.

**

Larger batteries may be mounted in an auxiliary UL864 Listed enclosure.

Two batteries are for the fire system and two batteries are for the audio system. 100HAVE may use up to 24Ah batteries.