FireSpy Tracker Installation Manual

41

Table 3-6: Wire Lengths for Panel Network RS485

Units

18 AWG

16 AWG

14 AWG

12 AWG

Part number of cable referenced for ratings

Belden

9571

9572

9580

9582

Resistance rating of cable

ohm/kFT

6.3

4.1

2.5

1.6

Capacitance rating of cable

pF/ft

22

29

27

30

Max distance, resistance candidate (worst case)

ft

7937

12195

20000

31250

Max distance, resistance candidate (best case)

ft

15873

24390

40000

62500

Max distance, capacitance candidate

ft

6818

5172

5556

5000

Max distance, wavelength candidate

ft

4269

4269

4269

4269

Max distance (worst case load distribution)

ft

4269

4269

4269

4269

Max distance (best case load distribution)

ft

4269

4269

4269

4269

Many factors are involved with communication circuits. Special considerations may need to be made for any specific job,
especially if these distances are exceeded.
Resistance-based distance calculations were performed by using Eq. C-1
Wavelength candidates are based on 25% of the wavelength of the circuit’s operating frequency, 57600 baud