Dc b, Appendix b. compatible devices – Harrington Signal Tracker T8000 - Install Manual User Manual

Page 33

Advertising
background image

D

C

B

HSI #780-0867

FireSpy Tracker Installation Manual

29

Appendix B. Compatible Devices

B.1

Startup delay for devices with alarm verification

The Tracker system includes an alarm verification feature that will result in a delay of the system alarm
signal from the indicated circuits.

The following statement applies to installations intended to meet UL864 requirements: The total delay
(control unit plus smoke detector) shall not exceed 60 seconds. No other smoke detector shall be
connected to these circuits unless approved by the local authority having jurisdiction.

The following statement applies to installations intended to meet California State Fire Marshal
requirements: For fire alarm verification feature (delay of fire alarm), the maximum retard/reset/restart
period (control unit plus detector) must be adjusted to 30 seconds or less.

For the devices below, the delay start-up time marked on the installation wiring diagram of the smoke
detector or on the installed smoke detector is to be used.

Circuits

Compatible smoke detectors with alarm verification

LCU and MCCLC, Class A and B

Apollo

55000-550, -650, -886

Harrington

TS8-DP, TS8-DH, TS8-DM

B.2

Addressable SLC devices (for use with T8000-LCU, T2000-MBCLC, and

T1-MB)

Each SLC circuit must use devices from a single series of compatible devices. Do not mix and match
unless otherwise noted. For example, do not use System Sensor and Apollo devices on the same circuit.

The following devices below may be used together on the same SLC circuit:

Harrington ISpy, TSpy, HSPS

Apollo XP95, Discovery

Air Products

B.2.1.

System Sensor

Harrington

Part No.

System Sensor Model

Description

Detectors

349-0508

1551

Ion smoke detector

349-0494

2551

Photo smoke detector

349-0495

5551

Heat detector, fixed temperature

349-0646

5551R

Heat detector, rate-of-rise

349-1048

1251B

Ion smoke detector – low profile

349-1046

2251, 2251B

Photo smoke detector – low profile

349-1056

2251BR

Photo smoke detector to be used with DNR/DNRW duct smoke detector

349-1047

2251TB

Photo/thermal multicriteria detector (Acclimate)

349-1071

2251TMB

Photo/thermal multicriteria detector (Acclimate)

349-1049

5251B

Fixed temperature heat detector, 135°

349-1059

5251H

Fixed temperature heat detector, 190°

Advertising