Da b c 3, Mbc-lc, Example slc wiring on mbc-lc – Harrington Signal Tracker T8000 - Install Manual User Manual

Page 25: Example zone wiring on cm, Figure 3-3: wiring on mbc-lc

Advertising
background image

D

A

B

C

3

HSI #780-0867

FireSpy Tracker Installation Manual

21

LINE INPUT

120VAC - 50/60Hz
230VAC - 50/60Hz

RS485

TO SERIAL

MODULES

A+

A-

B+

B-

+

-

- +

24VDC

P8

RS485

B+

A+

A-

B-

B+

A+

A-

B-

P7

NAC

B+

A+

A-

B-

P8

NAC

NC

COM

NO

NC

COM

NO

NC

COM

NO

P9

NAC

P6

J3

P3

P4

P5

NAC

SUPV ALARM

TROUBLE

ALARM

A+

A-

B+

B-

P9

SLC2

SLC1

MBC-LC

TYPICAL
STYLE Y

(CLASS B)

WIRING

10K

LINE

NEU/LINE

E

AR
TH

TYPICAL STYLE Z

(CLASS A)

WIRING

(end-of-line resistor

not needed)

CONTACTS RATED

10A @ 30VDC

10A @ 250VAC

1.0 POWER FACTOR

USE ONLY POLARIZED

DEVICES ON NACs

Polarity shown is alarm condition

ALL NACs ARE REGULATED 24 DC

SERIAL

PORT

24VDC

TO SERIAL

MODULES

BATTERY

CABLE

(TO P2)

+

+

+

+

10K

10K

B+

A+

A-

B-

J6

TO NETWORK

COMMUNICATOR

USB

PORT

ETHERNET

PORT

(OPTIONAL)

290-0119

TYPICAL

STYLE B (CLASS B)

WIRING

4.7k

4.7k

A+

A-

B+

B-

ZONE

TYPICAL

STYLE D (CLASS A)

WIRING

A+

A-

B+

B-

P10

ALL NACs ARE REGULATED 24 DC

NOTES

:

1) Use only smoke detectors that are listed in compatibility listing in

owner's manual.

2) Leave end-of-line resistors on unused circuits.
3) All terminals are rated for 14-22 AWG wire unless otherwise noted.
4) Combined load of all devices, including indicating appliances, is not to

exceed 7A.

J1 jumpers present

TYPICAL STYLE 4 (CLASS B) WIRING

SLC B-

SLC B+

Example SLC wiring on MBC-LC

Isolators (optional) separate each zone

TYPICAL STYLE 6 (CLASS A) WIRING

ZONE 1

SLC A-

SLC A+

SLC B-

SLC B+

SLC A-

SLC A+

SLC B-

SLC B+

ZONE 2

Isolators separate each detector
Remove J1 jumpers

Remove J1 jumpers

TYPICAL STYLE 7 (CLASS A) WIRING

A+

A-

B+

B-

ZONE

S

P

P

P

TO RC

Marks non-supervised circuits
Marks non-power-limited circuits

All others are supervised and power limited.
Segregate power-limited wiring from
non-power-limited wiring by at least 1/4 inch.

SUPERVISED AND POWER LIMITED

S

P

4.7k
4.7k

Example zone wiring on CM

J1

SW2

8

1

(RESERVED)

SW1

8

1

(RESERVED)

SW4

8

1

(RESERVED)

SW3

8

1

ON/OFF

Figure 3-3: Wiring on MBC-LC