FireSpy Tracker Installation Manual

14

T8000-A-CAB

T8000-EXP5

T8000-EXP5N

Size (inches)
Overall
Backbox

W x H x D
11.37 x 9.94 x 2.8
10 x 8.5 x 2

W x H x D
15.88 x 19.44 x 3.8
14.5 x 18 x 3

W x H x D
7.38 x 19.5 x 2.88
6 x 18.13 x 3.13

Knockouts
(1-1/8 dia)

3 top
3 bottom

4 top
4 bottom

2 top
2 bottom
4 each side

Module

Quantity of modules that may be mounted

T8000-CM

1

T8000-RC

5

5

T8000-RAN

1


2.4

Service use

The Tracker is suitable for the following NFPA72 service uses:

Table 2-21: Service uses.

Type

Service

Signaling

Required Equipment

Local (PPU)

A, M, SS, WF, R

Non-coded, march time

Proprietary (PPU)

A, M, SS, WF, R

Multiplex

Remote Station (PPU)

A, M, SS, WF, R

DACT
Reverse polarity

T-UDACT*
UCT

Central Station (PPU)

A, M, SS, WF, R

DACT

T-UDACT*

Auxiliary (PPU)

A, M, WF, R

N/A

UCT

Abbreviations for services:

A = Automatic fire alarm

M = Manual fire alarm

SS = Sprinkler supervisory service

WF = Waterflow alarm

R = Releasing device service

*

The T-UDACT is required equipment for these uses on the MBC and MBCLC. It is not required for these uses on the MB
because the MB has a built-in DACT.

2.5

Listings and approvals

ETL Listed:

Standard UL864

CSFM Listed

7165-0476:172 (T2000, T8000)

MEA/BSA

MEA 43-05-E, 43-05-E Vol 2 (T2000, T8000)