Trebor Quantum Series Di Water Heater User Manual

Page 18

Advertising
background image

PAGE 18

QUANTUM DI HEATER OPERATION / MAINTENANCE MANUAL

An enable button is provided that, when activated, will open the inlet valve
and allows the heater bank to be turned on. This function is active in
single and multiple output systems. This feature provides the ability to
safely disable a bank of heaters in a multiple outlet system.

After enabling the heater and when in local control mode, the on/off
button can be used to turn the heater on or off.

The temperature set point can be changed by pressing the “SP” button or
by pressing the current set point value on the left hand side of the screen.
The set point value can be changed on any page by pressing the set
point value on the left hand side of the screen.

The buttons on the bottom of the page will take you to the other pages.

4.2.b Alarm Status Page

Figure 4-2: Alarm Status Page (single & dual bank version shown)

The alarm page shows the alarm status of the heater, enables the user to
change the mode of the heater and allows the option of turning the
audible alarm (horn) off from the panel.

The mode of the heater can be toggled from “Local” mode to “Remote”
mode by pressing the button on the right hand side of the screen. The
button text changes from “Go to Local” to “Go to Remote” depending on
the current mode of the heater. Local mode allows the heater to be
turned on and off from the touch screen and disables turning the heater
on and off remotely. Remote mode allows the heater to be turned on and
off remotely using a software or hardware remote interface to the heater
(depending on the heater options) and disables turning the heater on and
off from the touch screen. The mode of the heater can only be changed
from the touch screen. Note that the mode status is also displayed on the
main page.

All of the heater alarms are listed on this page. When the heater system
enters an alarm state the heater is turned off and a horn sounds. This
horn can be turned off by pressing the reset button or by pressing the
turning off audible alarm off button on the alarm page.

Advertising