2 preventive maintenance schedule quantum – Trebor Quantum Series Di Water Heater User Manual

Page 38

Advertising
background image

PAGE 38

QUANTUM DI HEATER OPERATION / MAINTENANCE MANUAL

7.2 PREVENTIVE MAINTENANCE SCHEDULE

Quantum

Init

ial

S

tart

Week

ly

6 M

on

ths

Items

V

isu

all

y

Ins

pe

ct

Tighten

X

X

Process Control / Heater Element Status

X

X

X

Plumbing Leaks

X

X

X

Overpressure Relief Drain & Diaphragm

X

X

X

General Electronics

X

X

X

Solid State Relays (SSR’s)

X

X

X

Main Circuit Breaker

X

X

X

Distribution Breakers & Contactors

X

X

X

Branch Circuit Breakers

X

See following table for details on each item.

Verify torque at least every 6 months with a calibrated torque wrench. Do
not over tighten. Consult factory with questions.

Label

Part

Number

Description

Torque Value

MCB1

-

Circuit Breaker, 3 Pole, 480VAC, 60A - 225A

30.5 Nm / 270 in-lb

MCB1

-

Connection Terminal Block,6Wire,14-6AWG

6.0 Nm / 53.1 in-lb

CB1-4

98003862

Circuit Breaker, 3 Pole, 480VAC, 50A

5.6 Nm / 49.6 in-lb

CONT 1-4

98003544

Contactor, 50A, 400V, 3 Pole, 24VDC

2.5 Nm / 22.1 in-lb

SSR 1-8

98004141

SSR, 125A, 4-32VDC, 48-660V

3.7 Nm / 32.7 in-lb

CBH 1E1-12E2

98003865

Circuit Breaker, 2 Pole, 480VAC, 15A

2.5 Nm / 22.0 in-lb

F1-F4

98003253

Fuse Holder, 600V, 30A, 1 Pole

1.6 Nm / 14.2 in-lb

24VDC-PS

98003781

Power Supply, 10A, 320-575VAC, 3 Phase

0.6 Nm / 5.3 in-lb

TLM 1-2

98003897

8 Channel Temperature Monitor

0.4 Nm / 3.1 in-lb

98003505

Connection Block, NO, 24VDC

0.8 Nm / 7.1 in-lb

98003520

Connection Block, NC, 24VDC

0.8 Nm / 7.1 in-lb