Outputs / Other settings

Pulse output

31

29

37

Language

37

choose among all the available ones (see on page

43); scroll the variables by means of the

and

keys and confirm the selection with

. The avail-

ability (or non-availability) of the variable is clearly
indicated on the display.

•TYPE: type of alarm: up alarm (UP); down alarm (DOWN); up

alarm with latch (UP L): in this case the reset of the
output can only be manual; down alarm with latch
(D.L.): in this case the reset of the output can only be
manual; down alarm with disabling at power ON
(D.DO). Choose the desired alarm type by means of

the

and

keys and confirm it with

.

•SET ON: ON-alarm set-point. Select the value of the variable

by means of the

and

keys and confirm it with

.

•SET OFF: OFF-alarm set-point. Select the value of the

variable by means of the

and

keys and

confirm it with

.

•OUT: normally energized alarm (NE) or normally de-ener-

gized alarm (ND). Choose the desired function by
means of the

and

keys and confirm it with

.

•DELAY: delay on alarm activation. Select the desired delay

value in seconds by means of the

and

keys

and confirm it with

.

Only in case of controls of the power variables,
it’s necessary to select the resolution (position of
the decimal point) of the alarm set-point’s value.