Technical features

53

Digital outputs

60

56

64

Three-phase connections

RANGE (IMPEDANCE):
• AV5:

58V/100V (>500k

) - 1ADC (

0.3VA)

58V/100V (>500k

) - 5ADC (

0.3VA)

240V/415V (>500k

) - 1ADC (

0.3VA)

240V/415V (>500k

) - 5ADC (

0.3VA)

• AV7:

100/170V (>500k

) - 1ADC (0.3VA)

110/170V (>500k

) - 5ADC (0.3VA)

400/690V (>500k

) - 1ADC (0.3VA)

400/690V (>500k

) - 5ADC (0.3VA)

FREQUENCY RANGE: 40 to 440 Hz

Overload protection

• Continuous: voltage/current

AV5: 300V

LN

/520V

LL

/6A;

AV7: 480V

LN

/830V

LL

/6A

• For 1s: voltage/current

AV5: 600V

LN

/1040V

LL

/120A;

AV7: 960V

LN

/1660V

LL

/120A

Keypad

Four keys:

to enter the programming phase and confirm

the password, “UP”

and “DOWN”

to program the

values / select the functions and scroll the pages,

for

special functions.

Output specifications

ANALOGUE OUTPUTS (on request):
• Number of outputs: up to 4 (on request)
• Accuracy:

±

0.2% f.s.; (@ 25

°

C

±

5

°

C, R.H.

60% non-

condensing)

• Range: 0 to 20mADC, 0 to

±

20mADC,

Advertising