Technical features – Carlo Gavazzi WM3-96 User Manual

Page 58

Advertising
background image

59

Technical features

57

Energy Management

63

56

64

Additional errors

0 to

±

10mADC, 0 to

±

5mADC, 0 to 10VDC,

0 to

±

10VDC, 0 to

±

5VDC, 0 to

±

1VDC.

• Scaling factor: programmable within the whole range of

retransmission; it allows the retransmission management of
all values from:
0 to 20mADC, 0 to

±

20mADC, 0 to

±

10mADC,

0 to

±

5mADC, 0 to 10VDC, 0 to

±

10VDC,

0 to

±

5VDC, 0 to

±

1VDC

• Response time:

200ms typical (filter excluded, FFT ex-

cluded, 3

1

/

2

dgt indication)

• Ripple:

1% according to IEC60688-1 and EN60688-1

• Temperature drift: 200 ppm/

°

C

• Load:

0 to 20mADC:

600

; 0 to

±

20mADC:

550

0 to

±

10mADC:

1100

; 0 to

±

5mADC:

2200

0 to 10VDC:

10k

; 0 to

±

10VDC:

10k

0 to

±

5VDC:

10k

; 0 to

±

1VDC:

10k

Insulation: by means of optocouplers, 4000 Vrms between
output and measuring inputs, 4000 Vrms between output
and power supply inputs.

RS422/RS485 SERIAL OUTPUT (on request):
• Type: bidirectional multidrop (static and dynamic variables).
• Connections: 2 or 4 wires, max. distance 1200m, termination

directly on the module.

• Addresses: from 1 to 255, key-pad programmable.
• Protocol: MODBUS/JBUS
Data (bidirectional):
Dynamic (reading only)
System variables: P,P

AVG

,S, Q, cos

ϕ

, V

L

-

L

, f, THD energies,

status of digital inputs and status of the alarm output.
Single phase variables:
P

L1

, S

L1

, Q

L1

, cos

ϕ

L1

, V

L1

, A

L1

, THD

L1

, P

L2

, S

L2

, Q

L2

, cos

ϕ

L2

, V

L2

,

A

L2

, THD

L2

, P

L3

, S

L3

, Q

L3

, cos

ϕ

L3

, V

L3

, A

L3

, THD

L3

Static (writing only)
All programming data, reset of energies, activation of the static
output.