Object 0x6002 Total measuring range

SubIndex

0

Data type

Unsigned 32

Access

ReadWrite

Default

0x20000000 = 536870912 = 29bit

GXMMW_H

0x2000 = 8192 = 13bit

GXAMW_H

0x10000000 = 268435456= 28bit

GCMMW_H

0x1000 = 4096 = 12bit

GCAMW_H

0x80000000 = 2147483648 = 31bit ²

GBMMW_H

0x40000 = 262144 = 18bit

GBAMW_H

EEPROM

Yes

Significance

Total measuring range in steps optionally programmable.

Consequence: Number of revolutions = total measuring range / resolution
The maximum resolution (0x6502) must not be exceeded since otherwise the selected
total resolution range is too wide and will be rejected.

Values

1..n.. max. total measuring range in steps (0x 6502)
Entries ≠ default values are only effective with enabled scaling function (0x6000).

² with disabled scaling 32 bit


Writing in these object will clear any previously saved offset (0x6509, value = 0)


Important for multiturn encoder operation:
Continuous operation will be automatically supported where required.

Consequently, no specific relationship between total measuring range and measuring units per revolution
must be observed in the parameterization.

With enabled continuous operation and during power off, the encoder shaft may be turned up to ¼ of
the maximum permissible turns. Any excess turn may entail void position values which will be
signaled by a warning and call for a new referencing operation.

Non-continuous operation allows for an unlimited number of turns during power-off.

Proceed as below to find out whether your parameterization enables continuous operation:

 The „maximum possible number of turns“ provided by the encoder (depending on the configuration:

16 bits = 65536 or 13 bits = 8192) is multiplied by the parameterized measuring units per revolution.

 The result is devided by parameterized total measuring range.
 A remainder in the result (fractional digits) means continuous operation enabled.


Example: Parameterization with disabled continuous operation:

Max. possible number of turns

65536

(16 bits multiturn)

Measuring units per turn

:

3600

Total measuring range

29.491.200

(8192 x 3600)

Calculation:

65536 x 3600 / 29.491.200 = 8 (no remainder)


Example: Parameterization with enabled continuous operation:

Max. possible number of turns

65536

(16 bits multiturn)

Measuring units per turn

3600

Total measuring range

100.000

Calculation:

65536 x 3600 / 100.000 = 2359 remainder 29600