System considerations, 1 introduction, 2 general – Kontron CP384 User Manual

Page 65: 3 shielding, 4 debouncing for digital inputs, System considerations - 3, System considerations cp384

Advertising
background image

ID 31440, Rev. 01

Kontron Modular Computers GmbH

P R E L I M I N A R Y

Rev

N

r. = CP384 -

31440_

01 - 060

503/

144

233

Page 5 - 3

System Considerations

CP384

5.

System Considerations

5.1

Introduction

In addition to the basic specification requirements for the CP384 which have been addressed
in chapter 4, system integrators need to be aware of the overall system environment and the
application needs when designing the interfacing to the CP384. The following chapters address
a number of more apparent considerations which should be addressed, but certainly not all of
the possible situations which may be encountered. Many of the considerations presented here
are recommendations, but some are definite requirements if the CP384 is to successfully
achieve its purpose.

5.2

General

Care must be taken to ensure that proper grounding concepts are followed, and that the integ-
rity of the grounding system within the application be maintained.

Input wire routing should avoid proximity to high voltage or current sources.

Where possible input wiring length should be kept as short as possible.

5.3

Shielding

Input cable shielding in general is recommended.

The requirements for shielding can be seen primarily as a function of the system design and
environment, but empirical results must also be considered.

The CON2 connector has a metal housing which is connected to the CP384 shield and is iso-
lated from the system ground.

Ensure that if shielding is used that it is not in anyway connected to the system ground.

5.4

Debouncing for Digital Inputs

On the CP384 it is possible to select from a number of debouncing times, dependant on the
type of switches/sensors in use. For example, when using mechanical switches or relays to
switch the input, bouncing will always occur and therefore debouncing is necessary. A de-
bounce period may be selected from a range of values available, accessible via software in the
register depending on the settle time. Where it is known that an application does not generate
bouncing problems, the debounce period may be set to the default value.

Advertising