Rice Lake 920i Programmable HMI Indicator/Controller - ControlNet Interface User Manual

Page 17

Advertising
background image

Appendix

13

Param3 =

0, $ first field shall equal 0

,, $ path size,path

0x0000, $ descriptor

199, $ data type : 16-bit Unsigned Integer

2, $ data size in bytes

"Input Size", $ name

"", $ units

"", $ help string

4,454,20, $ min,max,default data values

0,0,0,0, $ mult,dev,base,offset scaling not used

0,0,0,0, $ mult,dev,base,offset link not used

0;

[Connection Manager]

Connection1 =

0x04010002, $ trigger & transport

$ 0-15 = supported transport classes (class 1)

$ 16 = cyclic (1 = supported)

$ 17 = change of state (0 = not supported)

$ 18 = on demand (0 = not supported)

$ 19-23 = reserved (must be zero)

$ 24-27 = exclusive owner

$ 28-30 = reserved (must be zero)

$ 31 = client 0 (don't care for classes 0 and 1)

0x44240405, $ point/multicast & priority & realtime format

$ 0 = O=>T fixed (1 = supported)

$ 1 = O=>T variable (0 = not supported)

$ 2 = T=>O fixed (1 = supported)

$ 3 = T=>O variable (0 = not supported)

$ 4-7 = reserved (must be zero)

$ 8-10 = O=>T header (4 byte run/idle)

$ 11 = reserved (must be zero)

$ 12-14 = T=>O header

$ 15 = reserved (must be zero)

$ 16-19 = O=>T point-to-point

$ 20-23 = T=>O multicast

$ 24-27 = O=>T scheduled

$ 28-31 = T=>O scheduled

,Param2,, $ O=>T RPI,Size,Format

,Param3,, $ T=>O RPI,Size,Format

,, $ config part 1 (dynamic assemblies)

,, $ config part 2 (module configuration)

"Discrete Exclusive Owner", $ connection name

"", $ Help string

"20 04 24 01 2C 96 2C 64"; $ exclusive output path

1_PLC5C_RTD_Format1 = 1_PLC5C_1794_Discrete_RTD_Format;