4 led status indicators – Rice Lake 920i Programmable HMI Indicator/Controller - ControlNet Interface User Manual

Page 8

Advertising
background image

4

ControlNet Installation and Programming Manual

2.4

LED Status Indicators

An LED array on the ControlNet module provides
status information for troubleshooting. LED 1
provides module status; LED 2 provides status
information for both Channel A and B; LED 3
provides status information that can apply to either
channel; LED 4 indicates the presence of a network
connection to the module.

Table 2-1 on page 4 summarizes the function of the
module and network status LEDs.

Figure 2-5. ControlNet Status LED Module

A single bi-color watchdog LED on the surface of the
ControlNet module provides diagnostic information
for debugging the module itself. Table 2-2 lists the
indications provided by the debugging LED.

1

2

3

4

Module Owned

Channel A

Channel B

Module Status

LED

Status

Description

LED 1

Module Status

Steady Green

Connection in run state

Flashing Green

Connecting, connection idle

Steady Red

Major fault

Flashing Red

Minor fault

LED 2

Channel A and B

Off

Module not initialized

Steady Red

Major fault

Flashing Red

Node configuration error

Alternating Red/Green

Self-test

LED 3

Channel A or B

Off

Channel disabled

Steady Green

Normal channel operation

Flashing Green

Temporary error (node will self-correct) or not configured

Flashing Red

No other nodes, or media fault

Alternating Red/Green

Network configuration error

LED 4

Module Owned

Off

No connection opened

Steady Green

Connection opened

Table 2-1. Module and Network Status LED Indications

Status

Description

Off

No power

Red, 4Hz

DPRAM check fault

Red, 2Hz

ASIC and FLASH ROM check fault

Red, 1Hz

RAM check fault

Green, 2Hz

Module not initialized

Green, 1Hz

Module initialized and running

Table 2-2. Debugging LED Indications