Installation

3

Figure 2-3. ControlNet Module

2.1.2

Installing ControlNet Option in the 520

Use the following procedure to install the ControlNet
Interface in the

520

indicator:

1. Disconnect indicator from power source.

Disconnect power before removing
indicator enclosure cover.

The

520

has no on/off switch. Before

opening the unit, ensure the power cord is
disconnected from the power outlet.

2. Place indicator on an antistatic work mat.

Remove screws that hold the enclosure cover
to the enclosure body.

Use a wrist strap to ground yourself and
protect components from electrostatic
discharge (ESD) when working inside the
indicator enclosure.

3. Carefully align the large option card

connector with connector J2 on the CPU
board. Press

down

to seat the option card in

the CPU board connector.

4. Use screws provided in the option kit to

secure the other end of the option card to the
threaded standoffs on the CPU board.

5. Route cables through cover supplied with the

option kit.

6. Reconnect power to the indicator.

7. The indicator automatically recognizes all

installed option cards when the unit is
p o w e r e d o n . N o h a r d w a r e - s p e c i f i c
configuration is required to identify the

newly-installed ControlNet interface to the
system.

2.2

ControlNet Network Connections

The ControlNet module includes the following
connectors:

Network Access Port (NAP), for temporary
diagnostic or configuration access

Two BNC connectors for ControlNet
Channels A and B

Feed ControlNet network cables through cord grip
(

720i

,

820i

and

920i

) or through the special cover

supplied for the

520

. Allow enough cable for routing

along inside of enclosure to connector on the
ControlNet module. Connect network cables to
connector on the ControlNet module (see Figure 2-3),
then use cable ties to secure network cables to the
cable tie mounts.

2.3

Address and Termination Switches

The ControlNet Interface address is set using switches
on the Profibus module. Figure 2-4 shows the address
and termination switches.

Figure 2-4. ControlNet Module Address Switches

Address Switches

Two rotary switches are used to set the decimal node
address, 1–99, of the ControlNet Interface (use
Address 0 if configuring the address in software.)
Note that the node address cannot be changed during
operation.

The left switch shown in Figure 2-4, marked

x10

, sets

the tens digit; the right switch,

x1

, sets the units digit.

(For example, to set a decimal address of 14, set

x10 =

1,

and

x1 = 4

.)

J2

ControlNet

Module

Network Access Port

(NAP)

ControlNet
Channel A

ControlNet
Channel B

MacID
Switches

x1

x10

LED Status Indicators

W arning

x1

x10

Address
switches