920i Flexweigh Systems Bulkweigher

10.When the delay after fill elapses, the fill gate closed input is scheduled. If it is open, the system is stopped in

the gate error state.

11. The system waits for scale out of motion and captures the full weight*.
12.The system prints the full weight.
13.The system increments the draft number, calculates the draft weight (full minus empty) adds it to the accumu-

lator, and prints the draft number and draft weight.

14.The system updates the display with the new accumulated weight and draft number.
15.The system turns on discharge output and keeps it on until the scale weight drops below the discharge weight

preset and the discharge delay elapses.

16.The system turns off the discharge gate output, and pauses during delay after discharge.
17.When delay after discharge elapses, check the discharge gate closed input. If it is not closed, the system is

stopped in the gate error state.

18.Unless the end cycle button has been pressed during the cycle, the system returns to step 5 for the next draft.

Pressing the E-Stop button and performing the end cycle push button routine is required to complete a cycle.

Note

If at any time during the sequence the printer goes offline, the printer offline error state will be
shown.