Load cell tb3 – Rice Lake DWM-IV Digital Weighmeter Model 5 User Manual

Page 8

Advertising
background image

3.2 Load Cell Connection

Connect the supplied seven position load cell terminal block to the load cell cable

according to the following table legend. Refer to the manufacturer of the load

cell(s) used for the wire color codes.

If the load cell does not provide the +/- Sense leads, jumper the +EXC to the +SEN

and –EXC to the –SEN terminals for proper operation. Insert the load cell terminal

block onto TB3 of the Model 5 circuit board. The unit is now ready for setup/calibration.

Apply power via the wall transformer.

Load Cell

TB3

+Excitation

+EXC

-Excitation

-EXC

+Signal

+SIG

-Signal

-SIG

+Sense

+SEN

-Sense

-SEN

Shield

SHLD

Advertising