CB901EX Operations Manual March 2011

BATTERY CHARGE MONITOR

The CB901EX battery voltage is monitored. If the input voltage is higher then 25 Volt then the

battery is being charged and D6 is ON. If AC power is lost or the battery charger fails then the battery
voltage will fall below the 25 Volt and D6 will turn OFF. At the same time Power Fail Alarm may be
sent to the DAD104 (if programmed) and the system is running on battery power. This alarm can only
be cleared by restoring the battery voltage to 25 Volt or higer.

PROGRAMMING

The following commands are used for this feature.
SCN

Set Call Number

SCID

Set Caller ID

SNA

Set Network Address

LCN

List Call Number

Example: Subscribers 10 has a DAD104 with network address 09 (hex). Power Fail Alarms from the
EX500 are to be sent to this DAD. First we assign call number 00 to the EX500 at Line Equipment
Number 4F(hex).

>SCN

cr

Call Number <10-99/*> : 00

cr

Line Equipment Number <$00..$3F> : 4F

cr

>SCID 00 EX500

cr

>SNA

cr

Call Number <10-99/*> : 00

cr

Node Type (1=Annunciator 2=Printer 3=Video) <1..3> : 1

cr

Network Address <$00..$FF> : 09

cr

>LCN

cr

Call Number <10-99/*> : 00

cr

Line Call In Priority
Equ. Number Caller ID Type QUE Alarm Call Annunciator Printer
Video
==== ========= ========== ==== ==== ===== ==== =========== =======
=====
$4F 00 EX500 ICM RING 1 5
09 ... ...
>