Problems controlling cellar temperature – Wine Guardian Ducted Split Wine Cellar Cooling Systems (WGS175) - Manual User Manual

Page 67

Advertising
background image

69

No power to thermostat Check wiring for loose broken or frayed
connections


Check transformer for 24v output

Power Switch Light is On and the Thermostat Light is On

Possible Cause

Solution


Thermostat is not set up properly Check thermostat set up in the guide.

Press fan ON switch to check evaporator fan
only.

Unit is Operating and Blows Evaporator Air, but the Supply Air is Not

Colder Than the Return Air from the Cellar


Possible Cause Solution

Thermostat not set up properly Check thermostat setup in the manufacture’s
thermostat guide

Compressor not operating High pressure switch open (button up)

Condenser airflow is blocked Remove blockage
Clean filter and coil (if needed)

Head Pressure (HP) switch is open Reset HP switch See reset instructions on
page 56

Problems Controlling Cellar Temperature

Problems are occurring even though the unit seems to be fully operational – evaporator fan blows
air into the cellar and compressor and condenser fan runs.

Advertising