Conair EARTHSMART UGH031-0209 User Manual

Page 19

Advertising
background image

Evaporator - The evaporator is a brazed plate heat exchanger where the

liquid refrigerant is allowed to evaporate (boil off) to absorb the heat (BTU)
from the process fluid. As the heat is absorbed, the process fluid is chilled.

High/Low Pressure Switches: The high/low pressure switches protect the

refrigeration system from unsafe operating levels. The high pressure switch
is factory set to open at 230 PSI and protects the refrigeration components
and personnel from potential damage or injury from excessively high
pressure. The high pressure safety must not be altered in the field for any
reason. The low pressure switch is factory set to open at 25 PSI and to close
at 35 PSI. The low pressure switch protects the chillers from possible damage
due to low operating pressure. The low pressure switch is field adjustable for
setpoints below 45°F {7.2°C}, contact a Conair representative for more
information.

H o w i t W o r k s : C o m p o n e n t L i s t i n g

( c o n t i n u e d )

D e s c r i p t i o n l

2 - 7

2

Description

IMPORTANT: Altering the High Pressure Switch setting will void any chiller warranty.

NOTE: The fan cycling switch

is adjustable when the chiller

is in an environment cooler

than 95°F {35°C}.

See

Appendix J entitled, Plumbing

Schematic.

Advertising