C h i l l e r C a p a c i t y a n d D e r a t e C h a r t

If operation of the chiller is less than 45°F {7.2°C}, a glycol and water mixture
is required.

See Operation section entitled, Filling the Chiller.

Ambient conditions affect air-cooled chiller operation and capacity. Standard
rating is at 95°F {35°C} entering air temperature. For ambient air conditions
greater than 95°F {35°C}, chiller derating will occur.

Standard chiller rating is 50°F {10°C} leaving water. For all other temperature
settings, output tonnage is altered as follows:

Output

Full Available %

Temperature °F {°C}

Capacity

60°F {15.5°C}

105%

50°F {10°C}

100%

45°F {7.2°C}

90%

40°F {4.4°C}

80%

35°F {1.6°C}

70%

30°F {-1.1°C}

60%

25°F {-3.8°C}

50%

20°F {-6.7°C}

40%

NOTE: Models must be positioned so that the condenser air inlet is no warmer than 95°F

{35°C} and the condenser air outlet is not blocked or restricted in any way.

NOTE: Locate models away from heat producing equipment. These items will affect ambi-

ent air conditions and the performance of the chiller.

NOTE: For chiller operation

below 45°F {7.2°C}, the

chiller’s control must be

configured properly. Contact

Conair Service.

IMPORTANT: A correct mixture of

glycol and water must be used as

process coolant for operation below

45°F {7.2°C}.

See Installation sec-

tion entitled, Filling the Chiller.