Conair EARTHSMART UGH031-0209 User Manual

Page 71

Advertising
background image

A p p e n d i x l

I - 1

C o n t r o l S e t u p

1/32 DIN Watlow SD controller Setup Sheet

Enter the following parameters

Menu

Parameter

Description

Setting

Set Up Page

Sen

Input sensor type

RTD

up & down for C-F

Temperature Units (degrees)

F

3 seconds

S.dec

Temperature Decimal Places

0

IS.en

Infosense

no

SP.Lo

Set Point Low Limit

40.0

SP.hi

Set Poing High Limit

65

Ftr.e

Input Filter

Both

Flt.r

Filter value - Seconds

5

Ot1

Output 1 function

heat

Ctr1

Control Method 1

ftb

Ftb1

Cycle time 1

10

PL 1

Power Limit 1

100%

PSL1

Output Power Limit Sacle Low 1

0%

PSH1

Output Power Limit Sacle High 1

90%

nLF1

Output Non-Linear Function 1

Off

Ot2

Output 2 Function - SP devaition

dE.AL

hys2

Alarm Hysteresis 2

1.5F

Lgc2

Alarm relay state on alarm - open

Al o

Lat2

Alarm 2 latching

nLat

dSP2

Alarm 2 Message

on

ACLF

AC line frequency

60

Unit

Units of Measurement

SI

I.Err

Input error latching

nLat

FAIL

Input Error Failure Mode

bPLS

Man

Manual Error Level

0%

dSP

Active Displays

nor

rP

Ramping Mode

off

LOC

Security Lockout

3

Programming

Adv and INF keys 6 seconds
P1

Temperature Units - C-F

F

P2

Low Temp Dev. alarm - A2.Lo

-4

P3

High Temp dev Alarm - A2.HI

20

P4

Proportional Band Hot Gas - pb.ht

3

P5

Intergral Hot Gas - It.ht

3.4

P6

Derivative - dE.ht

0.1