C l e a n i n g t h e B r a z e d P l a t e E v a p o r a t o r

Minerals and other contaminants produce deposits, scales, slime or algae on the heat
transfer surfaces exposed to water. Fouled surfaces could result in decreased cooling
capacity. Implement a water treatment program to slow the fouling.

CAUTION: Hot Surfaces

Always protect yourself from hot surfaces when working on the chiller, espe-
cially when working on or around the compressor and condenser. These
devices can reach over 160°F {71°C}. Allow these devices to cool before
performing any maintenance or troubleshooting.

Water quality should be maintained at a pH level of 7.4, but not less than 6.0 for
proper heat exchanger life.

To clean the brazed plate adapter:

1

Prepare a 5% solution of Phosphoric acid or Oxalic acid and water. Do not
heat the acid solution.

2

Disconnect and/or lockout main power to the chiller.

3

Shut the “To” and “From Process” valves (factory optional) and the drain
reservoir.

See Installation section entitled, Drain Connection.

4

Remove the chiller’s side panels.

5

Disconnect the pump from the heat exchanger. Install a cap in the opening of
the heat exchanger where the pump was connected.

M a i n t e n a n c e l

5 - 5

NOTE: These connections
may vary depending on the
model you have purchased.
Be sure to see the labeling on
your particular unit.

5

Maintenance

From Process inlet

To Process outlet

Fill/drain port

Water level gauge