Possible cause, Solution – Conair EARTHSMART UGH031-0209 User Manual

Page 57

Advertising
background image

Tr o u b l e s h o o t i n g l

6 - 5

6

Troubleshooting

Tr o u b l e s h o o t i n g

Problem

The chiller will not start.
(Control not illuminated)

Pump will not start.

Possible cause

Tripped circuit breaker.

Incorrect incoming voltage.

The power toggle switch is not turned
to the “On” or “I” position.

Open motor winding.

Internal overload has tripped.

Loose wire connection or defective
start capacitor.

CB2 circuit breaker has been tripped.

Solution

Verify resistance to ground. Reset
breaker.

See Troubleshooting section

entitled, Checking or Resetting the
Circuit Breakers.

Check incoming power source for
correct voltage and amperage as
detailed on the chiller nameplate.

See

Description section entitled,
Specifications: EarthSmart ECM Series
Chillers.

Turn the power toggle switch on the
control to the “On” or “I” position.

Contact Conair Service.

Auto-resetting. Allow the chiller’s
motor to cool and restart the chiller.

Check wiring diagrams,

see Appendix

H entitled, Electrical Schematic

,

replace connections or capacitor.

Verify resistance to ground. Reset
breaker.

See Troubleshooting section

entitled, Checking or Resetting the
Circuit Breakers.

Advertising