Problem

Compressor will not start.

Possible cause

High pressure switch has been tripped.

Circuit breaker has been tripped.

Loose wire connection or defective
start capacitor.

The actual “To Process” temperature is
below the setpoint.

Damaged or defective start capacitor.

Poor water flow.

Damaged or defective compressor.

Solution

Reset the High Pressure switch.

See

Operation section entitled, Resetting
the High Pressure Switch.

Verify resistance to ground. Reset
breaker.

See Troubleshooting section

entitled, Checking or Resetting the
Circuit Breakers.

Check wiring diagrams,

see Appendix

H entitled, Electrical Schematic

,

replace connections or capacitor.

Lower setpoint temperature value.

See

Operation section entitled, Starting the
Chiller.

Contact Conair Service.

Check pump rotation.

Clean the pump strainer.

See

Maintenance section entitled, Cleaning
the Pump Strainer.

Have a certified refrigeration
technician replace the compressor.