OPERATING MANUAL

PSEN op4F/H-A series

1003067-EN-02

43

7.5 EDM selection

This function enables users to select or exclude monitoring of the external switching devices.

BCM configuration: EDM selection

P

W

R

O

S

S

D

E

DM

A

CM

LEVEL

Activated

LED 4 ON yellow

Deactivated

LED 4 OFF

ACM configuration: EDM selection

To increase the safety level when EDM is OFF when the light curtain is commissioned,
ensure that the EDM input is not connected.

7.6 Reduced range

This function enables you to select the maximum operating range for the light curtain’s
assembly.
The table below summarises the different operating ranges for both resolutions, if the
reduced operating range is changed.

Resolution 30 mm

RX long range

RX short range

TX long range

20 m

6 m

TX short range

12 m

4 m

Resolution 14 mm

RX long range

RX short range

TX long range

7 m

2 m

TX short range

4 m

1 m


You can select this function via ACM for the receiver and via BCM for the transmitter.

Fig. 39 – Reduced range