7.9.8 Blanking mode in advanced configuration

A maximum of 5 blanking zones (fixed + floating) can be configured in ACM (however, at
least one separating beam is required between the zones).
The user can select the number of beams via ACM.

Reduced resolution

ACM configuration

The software calculates the maximum object size (in mm) that the light curtain can detect
without triggering a SAFE STATE.
The actual resolution of the light curtain changes based on the varying value that is
assigned to the parameter N.
The safety distance must be calculated based on the actual resolution.

Number of

hidden light

beams

Actual resolution of light curtain

14 mm

30 mm

1

23 mm

49 mm

2

33 mm

68 mm

3

42 mm

87 mm

4

51 mm

105 mm

Actual resolution based on the hidden light beams