9171 Installation Guide

Proprietary & Confidential

Canoga Perkins Metro Ethernet Routing Switch

Page 8 of 26

Cl2. For the specific requirement, see Table 2-3.

Table 2-3 Harmful Gas Threshold in the Equipment Room

Gas

Maximum concentration (mg/m3)

SO2

0.2

H2S

0.006

NH3

0.05

Cl2

0.01

2.1.5 Electromagnetic Susceptibility

Switches may be affected by the interferences from outside the system, which will have an effect on devices

through conduction of capacitance coupling, inductive coupling, electromagnetic wave radiation, common

impedance (including ground system) coupling and wires (power wire, signal wire and output signal wire, etc.).

The following attention should be paid to:

AC power supply system is TN system, and AC power socket should be single-phase 3-wire outlet

with protective earth (PE) so that filter circuit on devices can effectively filter interference from electric

grid.

Places where switches work should be kept away from strong-power radio transmitting station, radar

transmitting station, high-frequency high-current devices.

Electromagnetic shielding should be adopted when necessary, i.e. interface cables use shielded

cables.

Interface cables are required to be arranged indoors instead of outdoors to prevent signal ports of

devices from being damaged by over voltage and over current generated from lightning.

2.1.6 Laser Use Safety

9171 series of routing switches are Class 1 laser devices.

Do not stare at the optical interfaces directly when the optional optical interfaces of 9171 series of

routing switches are in operating mode, since light beam emitting from fiber has high energy which

may be harmful to retina.