. RS485 Bus Basic Knowledge

1. Connection and termination resistor

The RS485 standards require a daisy-chain connection between the equipment. There must be

termination resistors with 120Ωimpedance at both ends of the connection .

2. Transmission distances of RS485 Bus

When user selects the 0.56mm (24AWG) twisted pair wires as data transmission cable, the

maximum theoretical transmitting distances are as follows:

Baud Rate

Maximum Transmitting Distance

2400 Bps

1800m

4800 Bps

1200m

9600Bps

800m

3. Connection and termination resistor

The RS485 standards require a daisy-chain connection between the equipment. There must be

termination resistors with 120Ωimpedance at both ends of the connection (refer to Picture 31).

Please refer to Picture 20 for simple connection. “D” should not exceed 7m.

120Ω

120Ω

1#

2#

3#

4#

32#

. . . . .

Figure 31

120Ω

1#

2#

3#

31#

120Ω

D

A+

B-

A+

B-

. . . . .

. . . . .

Main controller

Figure 29