Setting Up Communications

Linking the PLC with the HI 1756 FC Feeder Control Module

To set parameters for the weigh scale module, you must establish communications with a
ControlLogix PLC. Follow the steps below to set up the communication link. You will
need a new or open RS Logix® 5000 project. For instructions, see your RS LOGIX 5000
manual.

Step 1. Look for a list of folders on the left side of the screen. Scroll to and select the

I/O Config folder, which will open a menu.

Step 2. Select New Module to display a list of modules.

Step 3. Select the Generic 1756 module to open the

Module Properties form.

Step 4. Enter the following connection parameters in

the appropriate fields:

 Name of Module
 Description of Module (Optional)
 Slot ID
 Input Assembly Instance:101 Size = 32
 Output Assembly Instance: 100 Size = 32
 Configuration Assembly Instance: 102

Size = 200

Step 5. Select DATA INT from the Comm Format

pull-down list.

Module Properties Dialog Showing General tab

Step 6. Open the Connection Tab.

Step 7. Set the RPI to 20 milliseconds or greater. Do not set this parameter lower than

20 milliseconds.

Step 8. Click Finish.