1. Command 1: Read calibration values. Use this command to read the rate and

weight calibration values.

2. Command 0x81: Write rate calibration values. Use this command to set the 7

rate calibration pairs.

3. Command 0x82: Write weight calibration. Use this command to set the 3 weight

calibration values: zero counts, low counts, and CalibK (weight per A/D count).

4. Command 0x83: Write both weight and rate calibration values.

The two commands below read and write configuration data. Each returns 52 DINT
values, which are the command, the channel, and the format word, followed by 49
parameter values, which are listed in the order of the parameter IDs.

5. Command 0x0F: Read configuration data.

6. Command 0x8F: Write configuration data.

The format word is like the one in the configuration data table, but in the least significant
word of the DINT rather than in the most significant word.

Note

The values written via these commands are NOT saved automatically to the non-volatile
memory and are lost on power down if no save to non-volatile command is given.