Setpoint report – Kistler-Morse KM Weigh II User Manual
Page 32
5-4
Chapter 5. Inputs and Outputs
11.
Press the F1 Key to select Val. The
display looks like this:
The unit of measure you set up in the
Units Menu shows in place of lbs.
12.
Use the keypad or the Up and Down
Arrow Keys to input the value where you
want the setpoint to activate. Press the
Enter Key to save the value in memory.
The display flashes a message acknowl-
edging your entry and returns to:
13.
Press the F2 Key to select Dead, to
set up a deadband for the setpoint. The
deadband value determines the point at
which a setpoint relay returns to its normal
on/off state. The display looks like this:
The unit of measure you set up in the
Units Menu shows in place of lbs.
14.
Use the keypad or the Up and Down
Arrow Keys to input the deadband value.
Press the Enter Key to save the value in
memory. The display flashes a message
acknowledging your entry and returns to:
15.
The setpoint relays can be configured
to change state either above (Hi) or below
(Lo) the setpoint value. Press the F3 Key
to select Hi/Lo. The display shows:
An asterisk indicates the current
selection.
16.
Press the F1 Key to select Hi or the
F3 Key to select Lo. The display flashes a
message acknowledging your selection
and then returns to:
17.
Press the Menu Key to access the
second page of the menu. The display
shows:
18.
Press the F1 Key to access Net/Grs.
The display shows:
An asterisk indicates the current
selection.
19.
Press the F1 Key to select Net or
the F3 Key to select Grs. The display
flashes a message acknowledging your
selection and then returns to:
20.
Press the F3 Key to select Fsafe.
The display shows:
An asterisk indicates the current
selection.
21.
Press the F1, F2, or F3 Key to
select the desired fail-safe condition. The
display flashes a message acknowledging
your selection and then returns to:
22.
Press the Esc Key. The display
returns to:
23.
Repeat Steps 10 through 22 to set up
additional setpoints if desired.
24.
Press the Esc Key to scroll up the
menu tree or press the Auto/Man Key to
return the display to vessel monitoring.
Setpoint Report
The Weigh II allows you to view the slot and
channel number of the setpoints of any
channel in the system. Follow this procedure.
SELECT FUNCTION
Net/Grs Fsafe
F1 F2 F3
FAIL-SAFE
ON *OFF NC
F1 F2 F3
SELECT FUNCTION
Net/Grs Fsafe
F1 F2 F3
SELECT SETPOINT
SP1 SP2 SP3
F1 F2 F3
SELECT FUNCTION
Val Dead Hi/Lo
F1 F2 F3
ENERGIZE HI/LO?
Hi * Lo
F1 F2 F3
SELECT FUNCTION
Net/Grs Fsafe
F1 F2 F3
SETPOINT
Net *Gross
F1 F2 F3
SELECT FUNCTION
Val Dead Hi/Lo
F1 F2 F3
SPX DEADBAND
> Y lbs
F1 F2 F3
SPX VALUE
> Y lbs
F1 F2 F3
SELECT FUNCTION
Val Dead Hi/Lo
F1 F2 F3