CONTROL PANEL OPERATING PROCEDURES

3-11

3.10 START/STOP LEVELS

The start and stop levels are the Air/Fuel Valve
positions (% open) that start and stop the unit,
based on load. These levels are Factory preset
as follows:

Natural Gas

Propane

Start Level:

25%

25%

Stop Level:

20%

21%

Normally, these settings should not require
adjustment.

Note that the energy input of the boiler is not
linearly related to the Air/Fuel Valve position.
Refer to Table 3-8 for the relationship between
the energy input and valve open position (%) for
a unit running on natural gas.


Table 3-8.

Relationship Between Air/Fuel Valve Position and Energy Input For Unit Running On Natural Gas

Air/Fuel Valve Position

(% Open)

Energy Input

(BTU/Hr)

Boiler Energy Input
(% of Full Capacity)

0 0 0

10% 0 0
20%

(Stop Level)

105,000

5.0%

30% 325,000 16%
40% 590,000 30%
50% 830,000 42%
60% 1,030,000 52%
70% 1,210,000 61%
80% 1,440,000 72%
90% 1,750,000 88%

100% 2,000,000 100%