INITIAL START-UP

BRASS HEX
HEAD CAP
(REMOVE TO
ACCESS GAS
PRESSURE
REGULATOR
ADJUSTMENT)

SSOV ACTUATOR WITH REGULATOR

Figure 4-4

Regulator Adjustment Screw Location

15. If necessary, adjust the iris air damper

shown in Figure 4-4 until the oxygen level is
within the range specified in Table 4-1.

AIR

INLET

IRIS AIR

DAMPER

(SEE DETAIL “A”)

USE 1/2"

WRENCH TO

INCREASE (CW)

OR DECREASE

(CCW) INLET AIR

IRIS ADJUSTMENT

DETAIL “A”

Figure 4-4

Iris Air Damper Location/Adjustment

16. Once the oxygen level is within the specified

range at 100%, lower the valve position to
80%.

NOTE

The remaining combustion calibration
steps are performed using the
Combustion Cal Menu

included in the C-

More Control System. The combustion
calibration control functions will be used
to adjust the oxygen level (%) at valve
positions of 80%, 60%, 45%, 30% and
20% as described in the following steps.
These steps assume that the inlet air
temperature is within the range of 50°F to
100°F.

17. Press the MENU Key on the front panel of

the C-MORE and access the Setup menu.
Enter password 6817 and then press the
ENTER

key.

18. Press the MENU Key on the front panel of

the C-MORE until Combustion Cal Menu
appears on the C-More display.

19. Press the ▲ arrow key until SET Valve

Position

appears on the C-MORE display.

20. Press the CHANGE key. SET Valve will

begin to flash.

21. Press the ▲ arrow key until the SET Valve

Position

reads 80%. Press the ENTER key.

22. Next, press the

down (▼) arrow key until

CAL Voltage 80%

is displayed.

23. Press the CHANGE key and observe that

CAL Voltage 80%

is flashing.

24. The oxygen level at the 80% valve position

should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.

Combustion Oxygen Level at

80% Valve Position

Oxygen %

± 0.2

Carbon

Monoxide

NOx

6.0 %

<100 ppm

< 20 ppm

25. If the oxygen level is not within the specified

range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the ▲ arrow key
increases the oxygen level and pressing the
down ▼ arrow key decreases the oxygen
level.

4-4