CONTROL PANEL OPERATING PROCEDURES

3-7

3.7. TUNING MENU

The Tuning Menu items in Table 3-5 are Factory
set for each individual unit.

Do not change these menu entries unless
specifically requested to do so by Factory-
Trained personnel.

Table 3-5. Tuning Menu

Available Choices or Limits

Menu Item Display

Minimum

Maximum

Default

Min Load Adj

-50°F

50°F

0°F

Max Load Adj

-50°F

50°F

0°F

FFWD Temp

30°F

245°F

Outlet Feedback

On
Off

On

Reset Defaults?

Yes

No

Are You Sure?

No


3.8. START SEQUENCE

When the Control Box

ON/OFF switch is set to

the

ON position, it checks all pre-purge safety

switches to ensure they are closed. These
switches include:
• Safety Shut-Off Valve Proof of Closure

(POC) switch

• Low Water Level switch
• High Water Temperature switch
• High Gas Pressure switch
• Low Gas Pressure switch
If all of the above switches are closed, the

READY light above the ON/OFF switch will light
and the unit will be in the Standby mode.

When there is a demand for heat, the following
events will occur:

NOTE:

If any of the Pre-Purge safety device switches
are open, the appropriate fault message will be
displayed. Also, the appropriate fault messages
will be displayed throughout the start sequence,
if the required conditions are not observed.

1. The

DEMAND LED status indicator will light.

2. The unit checks to ensure that the proof of

closure switch in the Safety Shut-Off Valve
(SSOV) is closed (Figure 3-3).

Figure 3-3.

Safety Shut-Off Valve

3. With all required safety switches closed, a

purge cycle will be initiated and the following
events will occur: