Start/stop levels, Control panel operating procedures – AERCO KC1000 Heater 2002 User Manual

Page 27

Advertising
background image

CONTROL PANEL OPERATING PROCEDURES

3-9

STEPPER

MOTOR

DETAIL "A"

DIAL
(DETAIL “A”)

BLOWER

BURNER

25

Figure 3-6.

Air/Fuel Valve In Ignition Position

8. With the unit firing properly, it will be

controlled by the temperature controller cir-
cuitry. The

FIRE R ATE will be continuously

displayed on the front panel bargraph.

9. Once the demand for heat has been

satisfied, the Control Box will turn off the gas
valve. The blower relay will be deactivated
and the Air/Fuel Valve will be closed.

Standby will be displayed.

3.9. START/STOP LEVELS

The start and stop levels are the fire rate
percentages that start and stop the unit, based
on load. These levels are Factory preset as
follows for natural gas and propane units:

• Start Level:

20% (All units)

• Stop Level:

13% (Natural Gas)

• Stop Level:

16% (Propane)

Normally, these settings should not require
adjustment.