SAFETY DEVICE TESTING

5-4

5.8 AIR FLOW FAULT TEST

1. Start the unit in manual mode and set the

fire rate between 25% and 30%.


2. Once the unit has proved flame, remove

either wire #154 or #155 from the blower
proof switch (see Fig. 5.5) located on the
air/fuel valve.


3. The unit should shut down and display

AIRFLOW FAULT DURING RUN.


4. Replace the wire previously removed from

the blower-proof switch and depress the

CLEAR button. The unit should restart.



WARNING!

ELECTRICAL VOLTAGES IN THIS
SYSTEM INCLUDE 120 AND 24 VOLTS
AC. POWER MUST BE REMOVED PRIOR
TO PERFORMING WIRE REMOVAL OR
OTHER TESTING PROCEDURES THAT
CAN RESULT IN ELECTRICAL SHOCK.

154

155

AIR/FUEL VALVE

BLOWER PROOF

SWITCH

TO FRAME

HARNESS

Figure 5.5

Blower Proof Switch Location and Wiring

5.9 SSOV PROOF OF CLOSURE

SWITCH

1. Set the unit’s

ON/OFF switch to the OFF

position. Place the unit in manual mode and
set the fire rate between 25% and 30%.


2. Remove the Safety Shut-Off Valve (SSOV)

cover to access the terminal connections.
See Fig. 5.6. For units with IRI gas trains,
access the terminal connections of the
downstream SSOV (see drawing SD-A-606
in Appendix E).


3. Remove either wire #149 or #148 from the

SSOV.


4. The unit should fault and display SSOV

SWITCH OPEN.


5. Replace the wire previously removed and

depress the

CLEAR button.


6. Start the unit.

7. Remove the wire again when the unit

reaches the purge cycle.


8. The unit should shut down and display

SSOV FAULT DURING PURGE.


9. Replace the wire on the SSOV and depress

the

CLEAR button. The unit should restart.

SSOV

ACTUATOR

COVER

SSOV

COVER

SCREW

Figure 5.6

SSOV Actuator Cover Screw Location