10 purge switch open during purge, Figure 5.7, Air/fuel valve cover location – AERCO KC1000 Heater 2002 User Manual

Page 41: 11 ignition switch open during ignition, Figure 5.8, Air/fuel valve purge and ignition switch locations, Safety device testing

Advertising
background image

SAFETY DEVICE TESTING

5-5

5.10 PURGE SWITCH OPEN DURING

PURGE

1. Set the unit’s

ON/OFF switch to the OFF

position. Place the unit in manual mode and
set the fire rate between 25% and 30%.


2. Remove the air/fuel valve cover by rotating

the cover counterclockwise to unlock it and
then pulling it towards you. See Fig. 5.7.


3. Remove one of the two wires from the purge

switch (Fig. 5.8) and start the unit.


4. The unit should begin to start, then shut

down and display PRG SWITCH OPEN
DURING PURGE.


5. Replace the wire on the purge switch and

depress the

CLEAR button. The unit should

restart.

VALVE

COVER

Figure 5.7

Air/Fuel Valve Cover Location

5.11 IGNITION SWITCH OPEN DURING

IGNITION

1. Set the unit’s

ON/OFF switch to the OFF

position. Place the unit in manual mode and
set the fire rate between 25% and 30%.


2. Remove the air/fuel valve cover (Fig. 5.7) by

rotating the cover counterclockwise to
unlock it then pulling it towards you.


3. Remove one of the two wires from the

ignition switch (Fig. 5.8) and start the unit.


4. The unit should begin to start and then shut

down and display IGN SWITCH OPEN
DURING IGNITION.


5. Replace the wire on the ignition switch and

depress the

CLEAR button. The unit should

restart.

IGNITION

POSITION

SWITCH

PURGE

POSITION

SWITCH

169

170

172

171

STEPPER

MOTOR

DIAL

BLOWER

BURNER

Figure 5.8

Air/Fuel Valve Purge and Ignition Switch

Locations

Advertising