3 maximum load adjustment, 7 over-temperature limit switch adjustments, Initial start-up – AERCO KC1000 Heater 2002 User Manual

Page 35

Advertising
background image

INITIAL START-UP

4-7

6. Press the

▲ or ▼ arrow key until Min Load

Adj is displayed.


7. Press the

CHANGE key. The display will

begin to flash.


8. Raise or lower the minimum load adjustment

in increments of one or two using the

▲ or

▼ arrow key. Increasing this value will
increase the outlet water temperature, while
decreasing it will decrease the water tem-
perature.


9. Press

ENTER to save the change. Allow

time for the system to stabilize between
adjustments


10. Repeat steps 5 through 9 as needed until

the temperature is stabilized at no more than
2 to 3 degrees above the setpoint.

4.6.3 MAXIMUM LOAD ADJUSTMENT

Check the temperature control at minimum load
as follows:

1. While monitoring the

FIRE RATE display,

create a maximum load on the system that
will yield a steady fire rate between 80% and
90%.

NOTE:

It may be necessary to open the outlet valve if it
was closed during minimum load adjustment to
obtain a sufficient flow rate for maximum
adjustment.

2. Wait several minutes to allow the outlet

temperature to stabilize under load
conditions.

3. Once the temperature has stabilized, the

OUTLET T EMPERATURE display should
read no more than 2 to 3 degrees below the
unit’s setpoint.


4. If the outlet temperature is stabilized, no

adjustment is necessary. If the unit is not
stabilized, proceed to step 5.


5. Press the

MENU key and select the Tuning

Menu.


6. Press the

▲ or ▼ arrow key until Max Load

Adj is displayed.


7. Press the

CHANGE key. The display will

begin to flash.

8. Raise or lower the maximum load

adjustment using the

▲ or ▼ arrow key.

Increasing this value will increase outlet
water temperature, while decreasing it will
decrease water temperature.


9. Press

ENTER to save the change. Allow

time for the system to stabilize between
adjustments


10. Repeat steps 5 through 9 as needed until

the temperature is stabilized 2 to 3 degrees
below the setpoint.


11. If the outlet temperature does not maintain

setpoint after a reasonable amount of time
and adjustment, contact your local AERCO
representative.

NOTE:

After performing Temperature Calibration and
prior to placing the water heater in service, be
sure to turn the Outlet Feedback option in the
Tuning Menu back to ON.

4.7 OVER-TEMPERATURE LIMIT

SWITCH ADJUSTMENTS

There are two Over-Temperature Limit switches
that turn off the unit when the outlet water
temperature becomes too hot. The lower over-
temperature limit switch is adjustable and should
be adjusted 20°F to 40°F above the operating
header temperature. The upper over-tempera-
ture limit switch is a manual reset device and is
not adjustable. It will shut the unit off if the water
temperature reaches 200°F.

DO NOT attempt to

adjust its setpoint.

To adjust the lower over temperature switch limit
switc

h:

1. Remove the wing nut from the top center of

the shell cap. Lift the cap off the shell.

2. The two over-temperature limit switches are

located at the top of the shell (see Fig. 4.6).
Do not

adjust the upper switch it has been

factory preset. Adjust the lower switch
between 20° to 40°F higher than the
maximum header temperature the unit may
see.

3. Replace the shell cap and wing nut.