With the compressed air system operating, energize the smart timer

board to begin pulsing. The smart timer must be put in manual mode.

Check to see that all solenoids are firing by placing a finger over the

exhaust port of one of the solenoid valves. When the solenoid valve

being checked is energized by an electrical pulse from the timer board

the finger at the exhaust port should feel a short blast of air. Quickly

move to the next solenoid valve in the firing order noting any valves that

do not fire or are stuck open causing a continuous airflow out of the

exhaust port of the valve. At this time note the quality of the compressed

air. It should be clean, dry, and oil free.

Allow the compressed air system to operate as long as possible to clear

the system of dirt, rust, scale, welding slag and metal chips that can

cause the diaphragm valves to stick.

The pressure at the compressed air manifold must recover to 80-90 psig

before each pulse. Make sure that there is adequate compressed air

delivery for full pressure recovery when all other systems connected to

the same air supply are operating at full capacity.